Outdoor Reset v Setback Thermostats

For years the Department of Energy has promoted the programmable setback thermostat as a means of saving energy.  In 2005 several field studies by the Department of Energy determined that in most cases the introduction of a programmable thermostat didn’t conserve energy and in some cases actually increased usage.  The biggest problem they found was that the thermostats either were not programmed correctly or in some cases were not programmed  at all.
Now along comes outdoor reset which adjusts the water temperature based on the outdoor temperature in an attempt to match the heat loss.  When coupled with a programmable thermostat it can be a recipe for customer discomfort.  As the water temperature is reduced the BTU’s into the space are reduced as well since the heat loss is less, the goal is to only put into the space what is leaving.  However if a setback thermostat is in play and not only are we trying to match the heat loss but raise the space temperature 10 degrees it could take a few hours.  To combat this many thermostat manufacturers have added to logic in their thermostat to learn a systems response time and come on a few hours earlier.
If a customer is setting their thermostat back at night to save energy they are better off to just set it and forget it and allow outdoor reset to manage the system.  The long run time to heat the house back up will offset any energy savings.
Or take a look at the next step in the energy saving evolution indoor feedback, with indoor feedback a system can tailor the water temperature to the actual heat loss, synchronize the zones to eliminate short cycling and ramp the water temperature up for those times when it has been setback or turned off.

Is Your System Balanced?


With the shift to small condensing boilers and lots of zones a new challenge has arrived , avoiding excessive boiler cycling.  What is an unbalanced system? In the typical condensing boiler installation it is a situation where the system side is flowing at a lower GPM and BTU rate than the boiler side.  An example is a small zone of baseboard using 2 GPM and 20,000 BTU connected to a 150,000 BTU boiler that can only turndown to 30,000 BTU.  There are several solutions to the problem including ramp delay of a boiler, variable speed boiler pumps, zone synchronization and buffer tanks.  Lee Cook of Capco Supply has put together a great article on using buffer tanks.

Does the right hand know what the left hand is doing?


Imagine driving your car down the road with your eyes closed and the pedal to the floor board waiting for your passenger to yell stop.  That is what happens when your boiler sits in the basement waiting for the zone control to tell it to go, stop, go and so on.  The boiler doesn't know if it is connected to one zone or to twenty, it just assumes that if I am told to go I must need all my BTU’s right now.

What if we could have the thermostats talk to each other and the boiler control with just two wires, and they could set the water temperatures and control the firing rate of the boiler.  Well the Tekmar House Control and communicating thermostats can do just that and so much more.